Product family · Carried
FXV3
Carried by Baltimore Aircoil Company, INC.
- Range
- 10°F
- Coil h
- 16 ft
- Coil w
- 14 ft
- Lower h
- 20 ft
- Lower w
- 14 ft
- Plenum h
- 22 ft
- Plenum w
- 14 ft
- Gearmodel
- FXV3-1224-xxx-10,15;FXV3-1224-xxx-20,30,40,50,60;FXV3-1224-xxx-75;FXV3-1426-xxx-15;FXV3-1426-xxx-20,25,30,40;FXV3-1426-x
- Maxcycles
- 6 per hour
- Motortype
- premium efficient totally enclosed single-speed reversible ball bearing
- Price pcd
- 271,840 USD
- Bleed rate
- 1.75 USGPM
- Start delay
- 15 s
- Process flow
- 800 USGPM
- Line lead max
- 100 ft
- Min coil flow
- 300 USGPM
- Overflow level
- 19.25 in
- Price standard
- 1,432,560 USD
- Turndown ratio
- 10:1
- Fan motor delay
- 15 s
- Inter fan delay
- 1 s
- Max switch freq
- 2.5 kHz
- Operating level
- 16.25 in
- Evaporation rate
- 8 USGPM
- Price insulation
- --- USD
- Max cleaning temp
- 100°F
- Max sodium nitrate
- 0.5%
- Max cleaning temp c
- 37.8°C
- Max butyl cellosolve
- 5-10%
- Max sodium carbonate
- 2%
- Max sodium hydroxide
- 5%
- Max cleaning duration
- 2 days
- Subfreezing operation
- allowed
- Recommended temp water
- 50°F
- Max sodium metasilicate
- 5%
- Max trisodium phosphate
- 0.5%
- Recommended temp glycol
- 45°F
- Max tetra sodium pyrophosphate
- 2%
From Baltimore Aircoil Company, INC.’s own documents · read October 17, 2026 · not verified by FactoryRegistry
Documents
Where this comes from — 13 documents
A machine read this from documents Baltimore Aircoil Company, INC. publishes on its own website, as of October 17, 2026. FactoryRegistry has not verified it; the documents are the authority.
- FXV/CXVB Rigging & Assembly Instructions: “FXV/CXVB Rigging & Assembly Instructions”
- FXV3: “FXV3”
- FXV3ClosedCircuitCoolingTower: “FXV3ClosedCircuitCoolingTower”
- Model: “Model”
- Model: “Model”
- Model: “Model”
- Model: “Model”
- FXVandFXV3ClosedCircuitCoolingTower, page 12: “overflow_level: 19.25 in”