Product family · Carried
UDC3500
Carried by Jackson Oven Supply INC · made by Honeywell International INC.
- Rtc
- None Real-Time Clock (RTC)
- Mode
- Duplex
- Rset
- 0.02-50.00 minutes per repeat or repeats per minute
- Gain4
- 0.1-9999 %
- Hipot
- 345 Vdc
- Loops
- Single Loop 2 Loops+Internal Cascade
- Pin14
- Shield
- Pin15
- RXD-
- Pin16
- RXD+
- Pin17
- TXD-
- Pin18
- TXD+
- Rset2
- 0.02-50.00 minutes per repeat or repeats per minute
- Input1
- TC,RTD,mV,0-5V,1-5V,0-20mA,4-20mA,-1-1V,0-10V,Relative Humidity (requires Input 2),Carbon/Oxygen/Dewpoint (requires Inpu
- Input2
- None,TC,RTD,mV,0-5V,1-5V,0-20mA,4-20mA,-1-1V,0-10V,Two HLAI instead of 1 LLAI
- Input3
- None,TC,RTD,mV,0-5V,1-5V,0-20mA,4-20mA,-1-1V,0-10V,Two HLAI instead of 1 LLAI,Slidewire Input for Position Prop. (requir
- Weight
- 3lb
- Propbd2
- 0.1-9999 % or 0.001-1000
- Propbd3
- 0.1-9999 % or 0.001-1000
- Rate up
- 0-9999 EU/HR
- Sp rate
- disable/enable
- Accuracy
- 0.05 % FS
- Final sp
- within setpoint limits
- Hotstart
- disable/enable
- Man rset
- -100 to +100 %output
- Rate2min
- 0.00-10.00 minutes
- Rate3min
- 0.00-10.00 minutes
- Rate4min
- 0.00-10.00 minutes
- Rate6min
- 0.00-10.00 minutes
- Rate7min
- 0.00-10.00 minutes
- Rate min
- 0-10min
- Rset3min
- 0.02-50.00 minutes
- Rset3rpm
- 0.02-50.00 rpm
- Rset4min
- 0.02-50.00 minutes
- Rset4rpm
- 0.02-50.00 rpm
- Software
- Standard Functions, Includes Accutune Math Option Set Point Programming (1 Program, 20 Segments) Set Point Programming P
- Gain4 alt
- 0.001-1000
- Max drops
- 15
- Pid range
- 1-4
- Prop band
- 0.1-9999%
- Rate down
- 0-9999 EU/HR
- Baud rates
- 4800,9600,19200,38400 baud
- Cycle time
- 1-120 seconds
- Default ip
- 10.0.0.2
- Gain range
- 0.1-9999 % or 0.001-1000
- Resolution
- 14 bits
- Comm modbus
- RS422/485 Modbus RTU, baud 4800-38400, length 2000ft twinax, 4000ft alt
- Cycle time2
- 1-120 seconds
- Gain7 range
- 0.1-9999 % or 0.001-1000
- Input types
- Thermocouple, RTD, Volt, Millivolt, Milliamp, Radiamatic, Slidewire (Input 3 only)
- Reset range
- 0.02-50.00 (min/repeat or repeat/min)
- Rj45 shield
- Shield
- Alarm relays
- 4
- Duplex modes
- manual,auto,disable
- Hipot analog
- 850 Vdc 2 s
- Power inrush
- 10A (4ms), then 225mA (90-264Vac) or 750mA (24Vac/dc)
- Reset6 range
- 0.02-50.00 (min/repeat or repeat/min)
- Seg2sp range
- within setpoint limits
- Analog inputs
- 3 universal inputs
- Comm ethernet
- 10Base-T Ethernet, length 330ft CAT5
- Comm infrared
- Serial Infrared, length 3ft, baud 19200-38400
- Ethernet type
- 10Base-T
- Hipot digital
- 850 Vdc 2 s
- Output2 motor
- 1/6 HP
- Relay voltage
- 115/230 Vac
- Rj45 rxd plus
- 1
- Rj45 txd plus
- 3
- Sampling rate
- 6 samples/s
- Security code
- 0-9999
- Communications
- None;Current Output #2+(4) Digital Inputs;Current Output #2+(4) Digital Inputs+Modbus RS-485 10 Base-T Ethernet (Modbus
- Hipot ac power
- 1900 Vdc 2 s
- Rate min range
- 0.00-10.00 minutes
- Rj45 rxd minus
- 2
- Rj45 txd minus
- 6
- Seg1ramp range
- 0-99 h 0-59 min
- Seg2time range
- 0-99 h 0-59 min
- Soak2dev range
- 0.000‑99.99 engineering units
- Temp stability
- ±0.0075% FS/°C
- Comm rs422 baud
- 4800-38400 baud
- Frequency rated
- 50 Hz ± 0.2 Hz, 60 Hz ± 0.2 Hz
- Fuzzy overshoot
- enable
- Impedance 0-10v
- 200 kΩ
- Impedance other
- 10 MΩ
- Jumper location
- Top of unit 3rd Input PWA W2 2nd Input PWA W1 MCU/Input PWA W2 W1
- Jumper position
- W1 Single Input; W2 Two HLAI
- Load resistance
- 0-1000 Ω
- Max drops short
- 31
- Prop band range
- 0.1-9999% or 0.001-1000
- Seg1pid options
- 1‑4
- Sp change range
- 5-15%
- Controller table
- Honeywell UDC3500 Universal Digital Controller manual page 40
- Impedance 4-20ma
- 250 Ω
- Analog resolution
- 16-bit
- Max link length m
- 600 m
- Power consumption
- 20VA (90-264Vac)
- Shock accel rated
- 0 g 30 ms
- Ambient temp rated
- 25 °C ± 3 °C
- Comm ethernet type
- 10Base-T
- Comm infrared type
- Serial Infrared (SIR)
- Input impedance ma
- 250 Ω
- Manual reset range
- -100 to +100 %output
- Max link length ft
- 2000 ft
- Stray rejection dc
- 120 dB (100 Ω source) / ±1 LSB
- Frequency operative
- 49 Hz to 51 Hz, 59 Hz to 61 Hz
- Frequency transport
- 48 Hz to 52 Hz, 58 Hz to 62 Hz
- Open collector sink
- 20 mA
- Output2 dual relays
- 2 SPST relays
- Setpoint rate range
- 0-9999 EU/h
- Shock accel storage
- 20 g 30 ms
- Slidewire impedance
- 100‑1000 Ω
- Ambient temp storage
- –40 °C to 66 °C
- Calibration accuracy
- ±0.05% FS
- Current output range
- 0-21 mA
- Input impedance volt
- 200 kΩ
- Setpoint rate enable
- 0/1
- Vibration freq rated
- 0 Hz
- Digital input voltage
- +30 VDC source
- Ethernet max length m
- 100 m
- Input impedance other
- 10 MΩ
- Shock accel operative
- 1 g 30 ms
- Shock accel transport
- 5 g 30 ms
- Solid state resistive
- 1 A
- Stray rejection ac cm
- 120 dB (100 Ω source) / ±1 LSB
- Temperature stability
- 0.01 % FS/°C
- Vibration accel rated
- 0 g
- Ambient temp operative
- 15 °C to 55 °C
- Ambient temp transport
- 0 °C to 55 °C
- Ethernet max length ft
- 330 ft
- Line voltage vac rated
- 120 V ± 1 V, 240 V ± 2 V, 24 V ± 1 V
- Line voltage vdc rated
- +24 V ± 1 V
- Max lead resistance tc
- 50‑1000 Ω/leg
- Output2 resistive load
- 5 A @ 120 V or 240 V or 30 VDC
- Vibration freq storage
- 0 Hz to 200 Hz
- Max lead resistance rtd
- 100 Ω/leg
- Relative humidity rated
- 10 % to 55 %
- Stray rejection dc 1khz
- 80 dB (100 Ω source) / ±1 LSB
- Vibration accel storage
- 0.5 g
- Vibration freq operative
- 0 Hz to 70 Hz
- Vibration freq transport
- 0 Hz to 200 Hz
- Output2 inductive load lr
- 3.5 A @ 30 VDC
- Output2 solid state relay
- 1 A @ 120/240 V (25 °C) 0.5 A @ 120/240 V (55 °C) 50 VA inductive (55 °C)
- Relative humidity storage
- 5 % to 95 %
- Stray rejection ac normal
- 60 dB (100 % span)
- Vibration accel operative
- 0.4 g
- Vibration accel transport
- 0.6 g
- Line voltage vac operative
- 90 V to 240 V, 20 V to 27 V
- Line voltage vac transport
- 90 V to 264 V, 20 V to 27 V
- Line voltage vdc operative
- 22 V to 27 V
- Line voltage vdc transport
- 20 V to 30 V
- Output2 inductive load cos
- 3 A @ 130 V or 250 V
- Electromechanical resistive
- 5 A
- Max lead resistance low rtd
- 10 Ω/leg
- Relative humidity operative
- 10 % to 90 %
- Relative humidity transport
- 5 % to 90 %
- Max lead resistance tc 100ω
- 100 Ω
- Max lead resistance tc 200ω
- 200 Ω
- Max lead resistance tc 500ω
- 500 Ω
- Output2 dual relays inductive
- 1 A @ 130 V or 250 V
- Output2 dual relays resistive
- 2 A @ 120 V or 240 V or 30 VDC
From Jackson Oven Supply INC’s own documents · read October 5, 2026 · not verified by FactoryRegistry
Documents
Where this comes from — 3 documents
A machine read this from documents Jackson Oven Supply INC publishes on its own website, as of October 5, 2026. FactoryRegistry has not verified it; the documents are the authority.
- Controllers: Honeywell UDC3500 Universal Digital Controller Product Manual - October 2005, page 1: “UDC3500 Universal Digital Controller”
- Controllers: Honeywell UDC3500 Universal Digital Controller Product Manual - October 2005: “Controllers: Honeywell UDC3500 Universal Digital Controller Product Manual - October 2005”
- Product Manual, page 25: “electromechanical_resistive: 5 A”
- Product Manual, page 22: “analog_resolution: 16-bit”