Lifeline® RHW-2 Two‑Hour Fire Resistive Cables

Made by Prysmian Cables and Systems Usa, LLC

Rating
600V
Material
Oxygen‑free Bare Stranded Copper
Standard
UL 2196, UL 44
Insulation
Cross‑linked Polyolefin (XLPO) LSZH
Fire rating
2‑Hour
Product class
Other insulated wire and cable (including automotive, and control and signal wire and cable) made of nonferrous metalsNAPCS 2033225000

From Prysmian Cables and Systems Usa, LLC’s own documents · read October 12, 2026 · not verified by FactoryRegistry

11 models

ModelSizeAmpacity75cAmpacity90c
H300701/0AWG150A170A
H300712/0AWG175A195A
H300723/0AWG200A225A
H300734/0AWG230A260A
H30074250kcmil255A290A
H30075300kcmil285A320A
H30076350kcmil310A350A
H30077400kcmil335A380A
H30078500kcmil380A430A
H30079600kcmil420A475A
H30080750kcmil475A535A